The FN-CTM is a City Tie Module used to connect the GEMC Fire Alarm Control Panel to a Local Energy type City Tie Monitoring circuit. The FN-CTM City Tie Module circuit provides the power necessary to trip the Master Box Trip Coil when the Fire Alarm Control Panel goes into alarm. The City Tie Circuit is capable of providing 1A for 0.5 seconds to operate the Master Box Trip Coil. The wiring is supervised to the Master Box by placing the EOL resistor device on the terminals of the FN-CTM City Tie Module.